May 16, 2008


image1 image2 image3 image4 image5 image6 image7 image8 image9 image10 image11 image12 image13 image14
 

VAV vs. low-flow: What saves more?

By Victor A. Neuman, PE

Laboratory facilities are expensive to build and even more costly to operate. Lab buildings with even moderate concentrations of chemical fume hoods can increase both construction costs and operating costs. This article presents some viable, higher-first-cost alternatives that generally result in significantly lower operating costs.

The first alternative is to use fume hoods with face velocities of 60 ft/min, which are variously referred to in the trade as “low-flow,” “low-exhaust-volume,” or “high-efficiency” fume hoods. The second alternative is to use variable volume controls on standard VAV fume hoods. A third alternative is to use low-flow fume hoods in conjunction with variable volume controls.

Before the analysis, a reality check: This article is aimed at fume-hood-heavy buildings. If you have one fume hood per 1,000 ft2 of laboratory or less, you do not have a fume-hood-heavy building. Many biology labs fall into the “not fume-hood-heavy” category, especially if using biological safety cabinets that are not hard-ducted to the exhaust system.

A fume-hood-light lab might still identify reasons to use low-flow fume hoods and/or variable volume controls, but such a choice won’t represent a major first cost. However, variable air volume can still save major operating costs even if the fume hood density is light. A special case of variable air volume operation is two-position constant volume. This type of operation is often the most cost-effective control system of its type, especially when the hours of operation of the laboratory can be predicted ahead of time. This system is often used as an occupied/unoccupied control system.

A short history of fume hood energy conservation A standard 6-ft hood takes 1,200 ft3/min (cfm) of exhaust air to operate at full open sash. The cost of a single cfm that needs to be heated, cooled, filtered, and moved every hour of the year, in an average electrical rate area, is about $3/cfm annually. The yearly air-conditioning bill for a single 6-ft fume hood can be $3,600/yr or more.

In the 1960s, the solution to this problem of high operating cost was the “auxiliary air” or “add-air” fume hood design. This design used raw outside air, cold in the winter and humid in the summer, introduced on the head of the fume hood user. I strongly recommend that lab users not select this type of hood. (Readers wanting more explanation can order a technical paper from ashrae.org on the disadvantages of auxiliary air fume hoods.)

Variable air volume (VAV) fume hoods became a major player in laboratory construction in the early 1980s. The main goal of VAV was to reduce operating costs, but properly executed designs also had major safety benefits. Safety benefits were achieved by improving flow monitoring accuracy and providing more accurate fume hood alarms. VAV fume hoods have sophisticated air-conditioning controls that reduce airflows whenever the fume hood sash is lowered. The average fume hood, including those using variable air volume controls, operates with face velocities of 100 ft/min (fpm).


Low-flow hoods in Gwinnett University Center, Lawrenceville, Ga. Photo: Mike Sinclair, courtesy of Labconco. Click to enlarge.
The new kid on the block is the low-flow hood. These fume hoods have made significant impact in the construction of lab buildings just in the past three years. Low-flow hoods use advanced aerodynamic design to contain chemical vapors using a smaller quantity of exhaust airflow. All of the major manufacturers have come out with fume hood models in this category. The hoods are most commonly operated at lower face velocities, such as 60 fpm. (Some individual cities, along with the entire state of California, mandate higher face velocities, but most jurisdictions will allow 60 fpm to be used.) Only in the past few years have fume hood manufacturers offered models that they would heartily endorse for use at this low an airflow rate.

Another special case is limiting the fume hood’s opening area. Horizontal sashes are one example of this. Another is the use of vertical sashes with sash locks at 18-in.” openings. These restricted sash opening designs can save first costs and energy but should be used only when the hood users can live with their smaller work openings. In older designs of fume hoods that require 100 fpm for safe operation, some safety problems have resulted when hood users have widened the openings in a restricted-area hood so that they operated at less than 100 fpm. If you have a hood that is only safe above 100 fpm, operating it at 50 fpm by defeating the 18-in. sash locks and opening it to 36 in. is not a good idea. In these cases, owners should consider using low-flow hoods operating at 100 fpm so that if safety devices are defeated by users the resulting 50 fpm face velocity is relatively safe.  

Below, I compare low-flow fume hoods operating at a constant volume in Alternative 1 with VAV hoods (operating, of course, with VAV controls) in Alternative 2. Some lab projects will be able to afford both low-flow hoods and variable air volume. This is alternative 3. This choice often represents the best of both worlds and will have an attractive simple payback.

Alternative 1: Choose a low-flow fume hood Despite the higher first costs involved, I have been impressed by most of the new low-flow hoods. Some of the new designs are significantly better than others, but I believe, on average, that the new low-flow hood designs are safer at 60 fpm than most of the older models at 100 fpm.

The standard fume hood, and even one of the low-flow designs, creates a whirling mass of air inside the hood. Airflow visualization looking in the side of the hood would show the contaminated exhaust inside the hood rolling in a circular vortex many times before exiting the hood. This leads to a buildup of contaminants inside the hood, although containment can be good with these designs.

Protector XStream hood airflow diagram. Image courtesy of Labconco. Click to enlarge.
Berkeley Low-Flow hood design. Image courtesy of LBNL. Click to enalrge.


Starting almost 10 years ago, a team led by Geoffrey C. Bell and Dale A. Sartor at the Lawrence Berkeley National Laboratory, Berkeley, Calif., revolutionized low-flow hood design. With several million dollars from the state of California and the Dept. of Energy, they came up with a design with an absolute minimum of turbulence and no whirling vortices. The diagrams above show their original design as well as a commercial model that reflects its influence.

One of the effects of this design, besides working very well at 60 fpm, is that levels of contaminants tend to build up less inside the hood. If there is a release of hood air due to operator movement or cross-drafts, a lower amount of hazardous contaminants would be entrained with it.

I have reviewed detailed factory and field data from a number of the top manufacturers on the performance of their low-flow fume hoods. For the most part, their performance is very impressive, and I recommend the use of these fume hoods with face velocities of 60 fpm, where allowed by code. However, not every fume hood manufacturer’s product will come up to the exacting standard of performance required by low-flow fume hoods.

Like newer, better equipment in every category, advanced low-flow fume hoods have a higher first cost. A standard 6-ft hood with accessories such as service fixtures, electrical receptacles, epoxy worksurface, and supporting acid and flammable base cabinets generally runs in the range of $1,200/ft. Low-flow fume hoods, such as the Labconco Xstream, are generally 20 to 25% higher, and will cost approximately $1,500/ft, installed. “If the high- performance fume hood is operated at a reduced face velocity, the payback period can be very quick,” according to Tom Schwaller, VP/sales, Labconco Corp.

For the purposes of payback analysis in this article, I assumed that the entire additional cost of $1,800 per 6-ft hood is reflected in the building cost. This will not be true on many projects. If your building has a lot of densely packed fume hoods, the choice of low-flow hoods at 60 fpm may so reduce the air-conditioning cost that the low-flow hood will be “free” to the project.

Also for the purposes of example, I assumed that the fume hood is operating at full sash height: 28-in. Fume hoods with restricted openings of 18-in. or less achieve cost savings of their own. If the 18-in. height is standard operating procedure, it reduces the potential savings from low-flow fume hoods or variable volume. Restricted-opening fume hoods have a long and successful history in laboratory buildings. Forcing the user to work in a smaller opening can save first cost in constructing the building, reduce operating costs, and improve safety. It is always safer to reduce the working opening of the fume hood in terms of promoting chemical vapor containment.

The only possible drawback to the reduced-opening hood is that many scientists will modify it to open 28 in. instead of 18 in., so as to gain greater access to their work. With most air-conditioning systems and most standard fume hoods, a hood operated at 28 in. when it is meant to operate at 18 in. will not be safe.

Many building maintenance directors like the low-flow fume hoods because they achieve first cost and operating cost savings with almost absolute reliability. The low-flow fume hood requires little more maintenance than standard fume hoods. Because these savings can be achieved without variable volume air-conditioning controls, the level of complexity of maintenance is reduced.

Alternative 2: choose variable volume controls With more than 20 years of installed history, there is quite a bit of solid experience with using variable volume fume hood controls in the laboratory. In some lab retrofits, installation of VAV has resulted in one-year paybacks and 50% reduction of air-conditioning costs.

The use of variable volume controls has made many labs easily adaptable to changing scientific requirements. A lab can be easily rebalanced by reprogramming the direct digital controls (DDC). In an old-fashioned constant volume building, a similar change in ventilation levels would mean a long and cumbersome process of changing fixed dampers and making field measurements.

The DDC systems needed for laboratory VAV entail better safety alarms and better recordkeeping and documentation capabilities. The monitoring function can reduce liability to the owner by verifying safe conditions are being met. It is also invaluable in responding to emergency conditions in the lab and promoting safety overall.

The main continuing resistance to VAV in the laboratory is its high first cost. Although VAV will recover its high first costs within one to three years of operation, most owners maintain that utility cost budgets are not related to construction cost budget. Accounting practices often make first costs hard to hide and tough to justify, whereas high operating costs might be easier to “bury.” Ironically, owners often will not increase the first cost of a building even when the operating cost savings over 20 years will pay for the increase 10 times over.

Another objection is to the increased complexity of maintaining these control systems. This objection lacks a great deal of validity. At its easiest level, a maintenance contract can be given to an outside company to keep the controls up and running.

I have been a big fan of VAV controls and hoods from their very start in early 1980s. They have many benefits to building owner and to the fume hood user.


Alternative 3: both of the above It is both technically feasible and cost-effective to combine low-flow fume hoods with variable volume controls. There is a lengthened payback period, and the decrease in costs is not great, but this is usually going to be the safest possible system.

The box above provides a cost and payback analysis of a theoretical 50-fume-hood facility. In this facility, low-flow hoods offered the fastest simple payback, but VAV and low-flow plus VAV schemes had lower annual operating costs. Each client would obviously have to weigh the first-cost, payback speed, and long-term operating variables to make an appropriate decision. There’s no blanket “correct” answer, but one thing is certain: the availability of new, advanced hood designs provides an excellent opportunity to create safer buildings that cost significantly less to operate.


Costs and paybacks for a 50-hood lab building

The building uses a 330 ft2 laboratory planning module and has one 6-ft. benchtop chemical hood per module. Assuming average utility rates and Midwestern U.S. weather patterns, $3/cfm will be used for 8,760 hr of fume hood usage. The base case is a 6-ft bench hood with 1200 cfm of exhaust, operating continuously year-round (CV). The cost of this system will be set as zero, and the other alternatives’ costs will be given as difference in cost compared with the base case.

Base Case: Older-style CV hoods,
minimal controls

• 1200 cfm 3 50 hoods/yr at $3/cfm/yr = $180,000/yr operating costs.
• Cost impact: Zero, since this is the base case and is lowest first-cost alternative.

Alternative 1: Low-flow hoods
• 720 cfm 3 50 hoods/yr at $3/cfm/yr = $108,000/yr operating costs.
• Cost impact: Assuming 6-ft hoods, additional first cost of $90,000. This conservatively assumes no savings from downsizing the air-conditioning system. It is also assumed that the air conditioning does not need to be increased to meet minimum ventilation rates in the lab.
•Simple payback: 1.25 years, with $90,000 repaid out of annual energy savings of $72,000.

Alternative 2: VAV hoods
• 1200 cfm 3 50 hoods for 1,000 hr/yr; 600 cfm 3 50 hoods for 1,000 hr/yr; 300 cfm 3 50 hoods for 6,760 hr/yr. $67,000/yr operating costs.
• Cost impact: Assume $6,000 additional first costs per fume hood for advanced safety controls and monitoring, or $300,000. This is conservatively not taking into account potential air-conditioning cost savings from downsizing the HVAC system because of the diversity of fume hood use.
• Simple payback: 2.65 years, with $300,000 in increased costs offset by $113,000 in annual energy savings.

Alternative 3: Low-flow hoods
with VAV controls

• 720 cfm 3 50 hoods for 1,000 hr/yr; 300 cfm 3 50 hoods for 7,760 hr/yr. $52,000/yr operating costs for an annual savings of $128,000.
• Cost impact: $390,000 (combined cost of advanced hoods and more expensive control system).
• Simple payback: 3 years.


Victor A. Neuman, PE, is senior mechanical engineer with LSW Engineers in San Diego. (www.lswsd.com). LSW is a 70-person mechanical-electrical consulting engineering firm with offices in Phoenix and San Diego that specializes in laboratories, hospitals, LEED-certified buildings, semiconductor manufacturing facilities, and commercial buildings.

 


 



© 2008 Advantage Business Media. All rights reserved.
Use of this website is subject to its terms of use.
Privacy Policy